For Better Performance Please Use Chrome or Firefox Web Browser

An Improved UFLS Scheme based on Estimated Minimum Frequency and Power Deficit

Abstract:

In the event of a power system disturbance, it is important that the decision to implement under frequency load shedding is based on both the minimum frequency and the magnitude of the disturbance. In this paper, we propose the use of higher order polynomial curve fitting to estimate the minimum frequency. If the prediction shows that the minimum frequency threshold will be violated, the magnitude of the total disturbance is estimated using the swing equation. In addition, the minimum amount of load that must be shed to restore the frequency just above the minimum value can also be directly calculated. Simulations are carried out for the considered Taiwan power system and the results prove the efficiency of the proposed technique.

 

Published in: 2019 IEEE Milan PowerTech

Date of Conference: 23-27 June 2019

DOI: 10.1109/PTC.2019.8810497

Conference Papers
Month/Season: 
June
Year: 
2019

تحت نظارت وف ایرانی